Operating Manual ISM – Intelligent Synchronization Module

4.7 UPS CONFIGURATION REQUIREMENTS

WARNING !

The installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.
Refer to the “Safety prescriptions - Installation
” described on page 6.



NOTE !


The UPSs are already correctly configured, if they have been ordered and supplied
with the ISM
.


Otherwise please make sure that UPSs connected with the ISM
mount:
P13 - IM0086 RPA Board with same software version as on the ISM.


Following software versions on P3 - IM0007 Control Board:

-

For SitePro units: U2, U3: version 2.08 or higher; U36: version 7.0 or higher.

-

For SG Series units: U2, U3: version 3.06 or higher; U36: version 7.0 or higher.