Modifications reserved

Page 21/34

OPM_ISM_OPT_10K_M50_0GB_V021.doc

Operating Manual ISM – Intelligent Synchronization Module

5 CONTROL

PANEL

5.1 CONTROL

PANEL

MAINTENANCE

MAINTENANCE

SYNC

ALARM

SERVICE

MUTE

LOAD

BYPASS

INVERTER

BYPASS

INVERTER

GROUP B

GROUP A

BYPASS OK

INVERTER OK

B SYNC TO A

A SYNC TO B

INVERTER OK

BYPASS OK

STS

SYNC MASTER

A

B

METERING

ALARMS

PARAMETERS

+

-

ENTER

AUTO

SYNC

OFF

ISM_LBS_Control panel_01

Fig. 5.1-1 General Control Panel


5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL

SYNC

ALARM

SERVICE

AUTO

SYNC

OFF

ISM_LBS_CP 1_01

Fig. 5.2-1 Control Panel – Part 1

SYNC
AUTO

SYNC AUTO – Green LED
When lit, it indicates that the sync command is active and that the inverters of
Group A and B will be synchronized to the selected “Super Master”.
The “Super Master” will be automatically chosen.

OFF

SYNC

SYNC OFF – Red LED
When lit, it indicates that the sync command is disabled due to one or both of the
following conditions:
• SYNC command is OFF;
• One of the two (2) UPS groups is not present.

ALARM

ALARM – Yellow LED
General alarm condition.
It blinks when one or more alarm is activated. The internal buzzer is ON.
The LED remains lighted (with alarm condition still present) and the buzzer stops
as the key “mute” has been pressed.

SERVICE

SERVICE – Yellow LED
When lit it indicates that a regular maintenance service is needed.
May be reset by a service technician only. See Section 8 – Maintenance.