Operating Manual SG Series 100 – 120 - 150 kVA

6.3 PARAMETERS

The parameters mode is entered any time the parameters button is pressed.

The LCD will display a series of screens containing the user parameters, accessible without password
protection.


The buttons perform the following functions:

metering Abandon

parameters mode and enter metering mode.

alarms Abandon

parameters mode and enter alarms mode.

parameters

Scroll forward to the next screen.

+

Scroll forward to the next screen.

Select from the current screen the parameter to edit.

ok

Start the editing for the currently selected parameter.


NOTE !

During parameters mode there is no means to perform scroll back on the display.



Example of operation within parameters mode:

Purpose: to correct a wrong telephone number previously stored in Tel2.

1 – Entering parameters mode (parameters). The first screen is displayed.

DATE AND TIME

D M Y

Date: 01.01.2006
Time: 12:45:07

metering

1

alarms

parameters

+

ok




2 – Scroll to the next screen (+). The second screen is displayed.

PROTOCOL SETUP

Modem enabled=N

Init=BEQV1X3&D0S0=2
Alarm= N

Delay=22s

metering

2

alarms

parameters

+

ok