2 complete ups shutdown (no load supply), Complete ups shutdown (no load supply) – GE Industrial Solutions SG Series 100 – 120 – 150 kVA Operating Manual User Manual

Page 49

Advertising
background image

Modifications reserved

Page 49/82

OPM_SGS_USM_M10_M15_0US_V030.doc

Operating Manual SG Series 100 – 120 - 150 kVA

7.2.2 Complete UPS shutdown (No Load supply)

NOTE !

The Load must be disconnected.

Initial status:

Load supplied from Inverter.


1. Press total off button.

Load is disconnected from UPS.
Rectifier is shut down and all output

and input contactors will be opened.

• LED’s, Rectifier, Inverter and Load are

OFF.

2. Open Q1 (Pos. O).

LED service check lights up.

3. Disconnect the Battery from the UPS in

case of External Battery.
• Wait 5 minutes for DC-Link Capacitors

discharge.

4. Disconnect the Utility.

• All LED’s are OFF.

END OF PROCEDURE

Advertising