6 parallel system shutdown (no load supply), Parallel system shutdown (no load supply) – GE Industrial Solutions SG Series 100 – 120 – 150 kVA Operating Manual User Manual

Page 72

Advertising
background image

Modifications reserved

Page 72/82

OPM_SGS_USM_M10_M15_0US_V030.doc

Operating Manual SG Series 100 – 120 - 150 kVA

7.4.6 Parallel system shutdown (No Load supply)

NOTE !

The Load must be disconnected.



Initial status: Load supplied from all Inverters.

First operated unit

All other units of the system

1. Press total off button on any one on the units.

Load is disconnected from UPS.
Rectifier and Inverter are shut down and all output and input contactors will be opened.

LED’s, Rectifier, Inverter and Load are OFF.

First operated unit

All other units of the system

2. Open Q1 (Pos. O) on all Units.

First operated unit

All other units of the system



Continue

Advertising