3.2.12 Electronic control system

All the control PCBs are installed in control box [Fig. 13].

Starting from the left, these are:

Fig. 13 Control box with control PCBs.

(1) NEKO control unit [Fig. 13-1] (Code 12) – internal
control unit with capacitor bank. Releases firing signal for

ED coil and provides indication of the capacitors charging.
NEKO control unit also blocks the firing signal until C-bank

is fully charged (~15 sec).

WARNING: NEKO unit requires a high quality signal. Be

sure, that voltage level is between 6 V…24 V DC and there
are no short spikes on signal (<3 ms). This may lead to

major defect of the NEKO control unit!

Fig. 13-1 NEKO control unit

(2) Internal voltage converter (Code 8) - converts
external supply voltage (-X3 :4/:5) to the internal

24 V DC. Required by controls (except for the drive

supply).

Fig. 13-2 Voltage converter 110 V/24 V DC.

(3) SU control unit.

1 2 3 4 3 2 1

Fig. 13-3 SU control unit.

(4) ST (a- trip) and UVR (r- release) control unit..

Fig. 13-4 UVR control unit

Fig. 13-5 ST control unit

10