GE Industrial Solutions GERAPID 8007R, 10007R WITH ARC CHUTES 1X2, 1X3 User Manual

Page 12

Advertising
background image

Control box terminals

(1) 12-pole

AC 400 V, 20 A

(4) 15-pole

AC 250 V, 8 A

Closing solenoid drive

1)

Rated voltage

AC 110 V - 240 V and DC 60 V - 250 V

Operating range

80 % - 115 % of rated voltage

Power consumption 60 Vdc drive

3000 W

Power consumption all other voltages

4500 W

Minimum command signal time

100 ms

Minimum interval between two closing operations ~8 s w/o NEKO installed; ~14 s with NEKO

Internal voltage converter

1)

Input: Voltage range

DC 33 - 85 V

Output: Voltage range

DC 24 V (±5%)

Current

6 A continuous

Model description

PCMD 150 48 S24W-GE

Input: Voltage range

DC 88 - 145 V

Output: Voltage range

DC 24 V (±5%)

Current

6 A continuous

Model description

PCMD 150 110 S24W-GE

Input: Voltage range

AC 115 - 240 V, DC 125 - 353 V

Output: Voltage range

DC 24 V (±5%)

Current

3 A continuous, 5 A for 100 ms

Model description

PCMA 70 S24W-GE or PCMAS 75 S24-GE

External power supply

with plug and socket unit

requires filtered DC 24 V (±5%)

Aux. contact HS 1…HS 10,

Rated operational voltage Ue/AC

230 V

OC trip target (code 10)

Rated operational current Ie/AC-15

1 A

Arc chutes indicator (code 17)

Conventional thermal current Ie/AC-12 (Ith)

10 A

Rated operational voltage Ue/DC

110 V / 220 V

Rated operational current Ie/DC-13

0.5 A / 0.3 A

Minimum current/voltage ratings

0,1 mA / 6 V DC

Contact duty (min. value)

DC 10 V / 2 mA

Shunt trip (a-release)

Rated voltage/power Uc/Pc

24 V / 100 W

Operating range: OFF

21.6 V - 26.4 V

UVR (r-release)

Rated voltage Uc

24 V

Zero voltage release

Operating range: OFF

< 4 V

Operating range: ON

24 V (±10%)

Power consumption

~ 10 W

ED impulse release

Energie source: Capacity

2000 µF

Charging voltage

300 V

Switching interval

max. 1/min with 10 consecutive operations

Endurance

1 000 operations with 1 operation per 180 s

Firing signal level / duration

6 - 24 V / 100 - 1000 ms

Charging signalization relay AC duty :

AC 250 V/ 0.5 A - AC 120 V /1 A

DC duty : DC 220V/0.1A - DC 125V/0.3A - DC 10V/3A

1)

Standard ambient conditions acc. to EN 50123-1 Attachement B. For meeting outside of this standard range, please contact GE.

Table 2a: Technical data of auxiliary circuits

Components

Technical datas of control circuits
Us / In

Closing

push-button -S1 (-X2 :4 / :5)

DC 24 V / approx. 10 mA

ST releasing

push-button-S2 (-X2 :6 / :7)

DC 24 V / approx. 4 A

UVR releasing

push-button -S2 ( -X2 :6 / :7)

DC 24 V / approx. 10 mA

push-button -S2 ( -X2 :8 / :9 )

DC 24 V / approx. 450 mA

Impulse coil tripping w/o NEKO

push-button -S3 (R=0.18 Ohm, Tau = 0.5ms)

DC 300 V / ~1100 A / 3 ms

Impulse coil tripping with NEKO

"firing signal" at ( -X2 :10 / :11 )

DC 6 V…24 V / approx.20 mA

Table 2b: Control circuits ( directional values to rate the components )

12

Design and specifications are subject to change without notice

DTR01807 rev.02 2010-02-16