3 electrical diagrams, 1 wiring code, Fig. 16 example code shown on the nameplate – GE Industrial Solutions GERAPID 8007R, 10007R WITH ARC CHUTES 1X2, 1X3 User Manual

Page 15: Indication of components

Advertising
background image

4.3 Electrical diagrams

4.3.1 Wiring code

The power circuits are not shown in the wiring diagrams
for clarity. The control circuit is presented as a typical
circuit diagram and is a combination of numbered basic

diagrams for closing, tripping and indicators.

The number of the complete diagram can be derived by
using the key numbers of the basic plan.

WARNING: Non-standard circuits may be issued for
special orders. Such circuits do not comply with the

diagrams in this instruction. In such a case an appendix is

delivered with the breaker.

Coding positions:

Key position:

1

/ 2 3 4 5 6 7

Breaker type

Aux.

voltage

supply

ED

impulse

release

Closing

drive

Aux.

tripping

device

Indicators

Aux. switches


EXAMPLE:

Key number:

37 / 1

0 20 10

01

2

Gerapid

rectifier

type

With

voltage

converter

Without

ED

and

NEKO

With

closing

drive

With

shunt

trip

With

POCT

indicator

With 5 aux. switches

Fig. 16 Example code shown on the nameplate.

Key

position

Key

number

Designation

Type
1 36 Gerapid
Auxiliary voltage
2 1 Voltage

converter

2

DC 24 V external supply

Tripping coil
3

0

Without ed impulse coil

1

With ed impulse coil

2

With ed impulse coil and
NEKO control unit

Drive
4

20

Solenoid drive with

SU control unit

Tripping device
5 00 Without

trip

unit

10

With

shunt

trip

20

With zero voltage release

Indication device
6 00 Without

indicators

01

POCT trip target

02

Arc chute indicator

03

POCT + arc chute indicator

Auxiliary contacts
7

1

3 auxiliary contacts

2

5 auxiliary contacts

3

10 auxiliary contacts


Indication of components

Q1

Closing drive coil

Q2, Q3

Impulse ED coil

S1 Push

button

„CLOSE“

S2

Push button „OPEN“ by means of ST or UVR

S3

Impulse coil firing signal

SU control PCB:

K1 Closing

relay

K2

Internal closing stop relay

1)

K3

Solid state relay


Shunt trip, zero voltage release PCB:

K1

Internal closing stop relay

1)

K2 Tripping

relay

HS11

Shunt trip self cut-off auxiliary contact


ED-tripping device with internal NEKO PCB:

K1

Voltage monitoring relay

K2

Internal closing stop relay

1)

1)

These relays are part of internal closing stop circuit.

It is a 24 V DC closed circuit, through all PCBs in the box,
except SEL. Serial connection of all relays is realized

through connections ( :5/:6) in each PCB. This circuit
provides priority of a tripping signal over a closing signal.
Additionally it prevents from closing if the internal supply
24 V DC lost at UVR PCB or NEKO PCB.

2010-02-16 DTR01807 rev.02

Design and specifications are subject to change without notice

15