4 troubleshooting – GE Industrial Solutions GERAPID 8007R, 10007R WITH ARC CHUTES 1X2, 1X3 User Manual

Page 38

Advertising
background image

7.4 Troubleshooting

Breaker does not CLOSE.

Breaker does not OPEN.

WARNING! Below operations are done with control voltage

connected. Only trained specialist or GE Service
representative shall perform them.
Risk of electric shock!

A) Closing drive doesn't operate electrically but it is still
possible to close the breaker manually by mean of the

hand lever.

A) Shunt trip does not operate. Breaker is able to CLOSE

and OPEN by means of hand lever.

1)

Check the supply voltage of the drive (-X2 :1/:2). The

voltage shall not be less than 80% of drive’s rated
voltage.

1)

Check points A2 to A5.

2)

Check the self cut off contacts HS11 and HS12.

2)

Check the supply voltage of the controls (-X3 :4/:5).

The voltage shall not be less than minimum input voltage
required for installed voltage converter

3)

Check the wiring and 24 V DC supply for ST PCBs.

4)

Check the continuity of shunt trip coils.

5)

Replace the ST PCB or ST coil if necessary.

3)

Calculate the voltage drop at both supply lines and

check for adequate wire size.

Contact GE Service in case of problem is not solved.

4)

Check the polarity of the supply connections.

5)

Check continuity of the control connections.

B) Zero voltage release does not operate. Breaker is able to

CLOSE and OPEN by means of hand lever.


Open the control box:

1)

Check points A2 to A5.

WARNING! Following operations are done with control
voltage connected. Only trained specialist or GE Service

representative shall perform them. Risk of electric shock!

2)

Check point B3 to B5.

3)

Check the continuity of UVR’s coils.

4)

Replace the UVR PCB or UVR coil if necessary.

6)

Check if the PCBs’ plugs are connected and

screwed.

Contact GE Service in case the problem is not solved.

7)

Check if there is 24 V DC available at output of both

voltage converters.

C) ED impulse release does not operate. Breaker is able to
CLOSE and OPEN by means of hand lever.

8)

Check the status of the red LED diode on the SU

PCB.


1) Check points A2 to A5.

-

Does not light – power supply failure;

2) Check the wiring and 24 V DC supply for NEKO PCBs.

-

Weak light – system ready to CLOSE;

3) Check the voltage level and timing of firing signal.

Voltage signal shall be between 6-24 V DC and duration

of minimum 3 ms.

-

Intensive red light – system not ready to

CLOSE. Closing STOP circuit is active, or NEKO PCB is

not charged, or “anti-pumping” is active for 15 sec.

4) Check if the NEKO is signaling C-bank charging correctly.

Relay is closed when NEKO is ready to operate.

9) Check if the Closing STOP circuit is not open. Measure

voltage at SU PCB, (-X12 5:/:6). There shall be ~24 V DC

available for actuation of “closing stop relay”.

5) Check the continuity of ED coils.

6) Replace the NEKO PCBs if necessary.

10)

Replace any ST/UVR/NEKO PCB if necessary.

11)

Replace the SU control PCB.

Contact GE Service in case the problem is not solved.

12)

Switch OFF the power at control box! Check

continuity and resistance of solenoid winding. Replace
the solenoid in case of winding breakage.

Contact GE Service in case the problem is not solved.

B) Closing drive operates electrically, but it is not possible

to keep contacts closed.

1)

Check the forced tripping release (if installed). A

permanently blocked tripping device, during closing
operation, will cause closing failure and force contact

opening.

2)

Check contact system area. Look for any parts that

may be stuck between contacts or into mechanism

module.

3)

If the zero voltage release is installed, check

connection of (–S2) pushbutton..

Open the control box (only when UVR is installed).
4)

Check the wiring connections for UVR PCBs.

5)

Check 24V DC supply for the UVR PCBs.


Contact GE Service in case the problem is not solved.

38

Design and specifications are subject to change without notice

DTR01807 rev.02 2010-02-16

Advertising