-S2

• The closing STOP signal is provided for resetting K2 on the SU-control circuit. It effects with priority in switching

OFF (by ST or UVR) before switching ON. Once switching ON and OFF signals are simultaneous, switching OFF
command will stay longer, than switching ON. It means, that OFF command is a master command.

• The coils energize for short time only. After main contacts opening, switch HS 11 and HS12 cuts off both trips.

• Manual closing of the breaker, while –S2 contact is closed, leads to overheating of ST coils and its damage.

Fig. 21 Shunt trips control circuit

-K1

-X113: ST PCB


[ 4 ]



[ 3 ]

[ 5 ]

[ 8 ]

[ 6]



[ 7 ]






[ 10 ]

[ 9 ]





[ 1 ]




[ 2 ]

-X110/111

](-)

24 V DC

] (+)


[ 7

[ 9

1

ST

ST coil


-K1

Closing

STOP relay

Key position - 5

Key number - 00: Without shunt trips or zero voltage releases.

Key number - 10: With shunt trips.

37/ _ _ _ X _ _ _

-X2


[ 6



[ 7 ]

]

-X2


[ 8 ]



[ 9 ]

Cut-
con

-HS

off

tact


11

-X13: ST PCB


[ 4 ]



[ 3 ]

[ 5 ]

[ 8 ]

[ 6 ]



[ 7 ]






[ 10 ]

[ 9 ]





[ 1 ]


[ 2 ]

-X10/11


[ 7

[ 9

](-)

24 V DC

] (+)

2

ND

ST coil


-K1

Closing

STOP relay

Cut-off
contact

-HS12

-K1

22

Design and specifications are subject to change without notice

DTR01807 rev.02 2010-02-16