X116: neko pcb, 37/ _ x – GE Industrial Solutions GERAPID 8007R, 10007R WITH ARC CHUTES 1X2, 1X3 User Manual

Page 19

Advertising
background image

-X116: NEKO PCB



[ 1 ]

(+)




(-)

[ 2 ]




[ 9 ]



[ 10 ]


[ 5 ]



[ 6 ]




[ 3 ]

(+)

(-)


[ 4 ]




[ 11]


[ 12 ]

Impulse switching

Isolating Transformer


Charging Control



Charging Voltage

Control

Signals


-K1



-K2

Closing

STOP relay

C-bank and output circuit

Input circuit for firing signal

Firing signal

control

-X110/111


[ 8 ]

(+)

24 Vdc


[ 6 ]

(-)

-X3


[ 10 ]

C-bank

charging

signalization

[ 11 ]

-X2


[ 10 ]

Tripping

Cut-off

contact


i.e. HS 9

Provided

by user!

signal

6V...24V


[ 11 ]

-Q3


ED impulse

coil no.2

Key position - 3

Key number - 2: With ED coil and internal NEKO control unit.

37/ _ X _ _ _ _ _



• Firing signal at (-X2 :10/:11) is processed by opto-coupler. Pay attention to the polarity!

• Closing STOP signal is provided to lock CLOSE command, until capacitors are fully charged.
• Be sure that voltage level is between DC 6 V - 24 V and there are no transient spikes (<3 ms) on firing signal.

This can lead to major defect of the NEKO control unit!

Maximum duration of the firing command must not exceed ~1 sec. Longer signal might cause NEKO failure! It is
recommended to use one of HS auxiliary contacts connected in series with firing circuit (-X2 :10). It will

automatically cut off the firing circuit after breaker opening.

Fig. 19b 2 impulse release system with ED coil and internal NEKO control unit

nd

2010-02-16 DTR01807 rev.02

Design and specifications are subject to change without notice

19