GE Industrial Solutions SG Series 50 & 80 kVA Operating Manual User Manual

Page 30

Advertising
background image

Modifications reserved

Page 30/82

OPM_SGS_USM_50K_80K_0US_V030.doc

Operating Manual SG Series 50 & 80 kVA

3 – Change to 4800.

metering

3

alarms

parameters

+

ok

EDIT MODE

PRINTER BAUDRATE

4800
+ SCROLL - CHANGE

4 – Press ok: the screen will return to parameters mode saving the new value.

PRINTER SETUP

Baud=4800

Parity=O

Bits=8 Handshake=XON
Print All = N

metering

4

alarms

parameters

+

ok

Type 3: Boolean parameters used to simulate command buttons.

The Boolean parameters have a range of Yes/No.
Only the user performs the modification of the value.

These “Type 3” parameters are used to initiate an action. There are two possibilities:

A

1 – The user wants the UPS to start the action => the user sets the parameter to “Yes”.

2 – The UPS finishes the action => the UPS sets the parameter to “No”.

B

1 – The user wants the UPS to start the action => the user sets the parameter to “Yes”.

2 – The user wants to abort the action => the user sets the parameter to “No”.


The actions that can be performed using such software buttons are:

Print the metering information.

Print the last 256 events.

Print the values of the parameters.

Print all the information obtainable from the UPS.

Returning from the Edit mode

Normally the ok button is used to return from the Edit mode.
Then the UPS will perform some validity tests on the new value.
If these tests are successful then the new value is saved and used.
If these tests fail the Edit mode is not exited.

NOTE !

The validity tests performed by the UPS are not exhaustive.
You should not rely exclusively on these tests.
Care should be taken when modifying the values of the parameters.

For all parameters except the LCD Contrast parameter the new value is saved and used after the ok
button was pressed.

In the case of the LCD Contrast parameter the new value is used immediately in order to obtain a better
visual feedback.