7.1 PROCEDURES FOR SINGLE UPS

7.1.1 Start-up of the SG Series

Verify with open front door: Switch Q1 and Q2 must be open (Pos. O).

1. Connect the Utility power on the UPS.

(In case of separate inputs for Rectifier and

Bypass, connect both).
• Power supply starts up.

Indicated with flashing alarm and buzzer
sound
.

• LED’s as indicated will be lit.
• Press mute, to reset alarm and buzzer.

2. Close Q1 (Pos. I).

Bypass Utility connects to the output.
Rectifier starts automatically, blinking LED

indicates Soft-start.

At the end of Rectifier Soft-start, LED

remains lit.

3. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of

External Battery.

4. Press inverter on ( I ) key.

• Soft-start of Inverter indicated with

blinking LED.

• At the end of Soft-start the LED remains

lit.

• Automatic transfer from Bypass to

Inverter.

UPS output LED indicates Load on

Inverter.

The LCD must display on the main screen the status “LOAD ON INVERTER”.

END OF PROCEDURE

NOTE !

The Battery must be charged for at least 10 hours, in order to ensure the full
backup runtime in the case of a Utility Failure
.