Operating Manual SG Series 50 & 80 kVA

7.2.3 Restore to normal operation after “total off”

View of the panel after pressing the button
total off”
.

All Contacts are open.

Rectifier, Inverter and Static-Switch
shutdown.

1. Reset total off by pressing and holding

the “total offbutton and the inverter
on
( I )
key simultaneously until the
Rectifier starts.

2. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in case of

External Battery.

3. Press inverter on ( I ) key.

• Soft-start of Inverter indicated with

blinking LED.

• At the end of Soft-start the LED

remains lit.

• UPS output LED indicates Load on

Inverter.

The LCD must display on the main screen the status “LOAD ON INVERTER”.

END OF PROCEDURE