Operating Manual SG Series 50 & 80 kVA

7.4.3 From Manual Bypass (Q2) to normal function VFI

Initial status: Load supplied from Manual Bypass.

All Q2 of the system closed.

First operated unit

All other units of the system

1. Connect the Battery to all Units by closing the external Battery Switch(es) or Fuses.

2. Close Q1 (Pos. I) on all Units.

The Rectifiers will start automatically and at the closure of Q1 of the last Unit, the Bypass
of all Units will be activated.

First operated unit

All other units of the system

3. Open Q2 (Pos. O) on all Units.

First operated unit

All other units of the system