MAN0373-01 13 APR 2000 PAGE 15

CH.3

CHAPTER 3: OPTION CARD CONFIGURATION (USING AF-300 KEYPAD)

3.1

Keypad Functionality

The keypad functions and operations are covered in the drive manufacturer documentation. This
document is concerned only with describing the keypad functions that are used to configure the option
card and effect the option card operation.

3.2

Option Card Configuration Parameters

The following table lists and describes the parameter settings used to configure the Option Card
parameters. As described previously, Genius devices have the capacity to broadcast 128 bytes (64
words) of global data and receive 128 bytes (64 words) of directed data. The Option Card is limited to 24
bytes (12 words) of global data and 20 bytes (10 words) of directed data. The parameter values can be
changed using the instructions found in the drive manufacturer’s documentation.

Table 3.1 – Parameter Settings

Option

Card

Parameter

Description

Valid Input

Values

Default Value (o31 = 255)

o30

Bus Address

0-31 (1-30

typical)

1

o31

Baud Rate

0 = 153.6K EXT

1 = 153.6K STD

2 = 76.8K

3 = 38.4K

255 = Reset parameters to
default

0-3

255

1 = 153.6K standard

o32

Global Data Length

0 - 12

7

o33

Directed Data Length

0 - 10

4

o34

User Defined Broadcast Data 1

1-254

0;255*

M14 Operating State

o35

User Defined Broadcast Data 2

1-254

0;255*

M06 Actual Frequency

o36

User Defined Broadcast Data 3

1-254

0;255*

M11 Output Current

o37

User Defined Broadcast Data 4

1-254

0;255*

M10 Motor Output

o38

User Defined Broadcast Data 5

1-254

0;255*

M16 Fault Memory 0

o39

User Defined Broadcast Data 6

1-254

0;255*

M07 Actual Torque

o40

User Defined Broadcast Data 7

1-254

0;255*

M01 Frequency Command

o41

User Defined Broadcast Data 8

1-254

0;255*

255

o42

User Defined Broadcast Data 9

1-254

0;255*

255

o43

User Defined Broadcast Data 10

1-254

0;255*

255