GE Industrial Solutions HE300GEN150 User Manual
Page 24
MAN0373-01 13 APR 2000 PAGE 25
CH.5
CHAPTER 5: AF-300 DRIVE PARAMETERS
5.1
Drive Parameter Descriptions
The following table contains the communication index number used for mapping the drive parameters into
Genius I/O. Each communication index number is associated with a specific parameter. The details
about the specific parameters can be found in the manual supplied with the drive.
Table 5.1 – Communication Parameter Index
Comm
Index
G11
data
E11
data Hex
Description
Keypad
Data
Format
0
-
-
0
1
S01
S01
1
Frequency command
2
2
-
-
2
3
-
-
3
4
-
-
4
5
S05
S05
5
Frequency command
5
6
S06
S06
6
Operation command
14
7
S07
S07
7
Universal Do
15
8
S08
S08
8
Accel Time
3
9
S09
S09
9
Deccel Time
3
10
S10
S10
A
Driving Torque Limit
5
11
S11
S11
B
Braking Torque Limit
5
12
S12
S12
C
Universal Ao
2
13
-
-
D
14
-
-
E
15
M01
M01
F
Frequency (Motor speed) setting (final)
2
16
-
-
10
Torque command (final)
17
-
-
11
Torque current command (final)
18
-
-
12
Magnetic flux command (final)
19
M05
M05
13
Frequency setting (final)
5
20
M06
M06
14
Actual frequency
2
21
M07
M07
15
Actual value of torque
6
22
M08
M08
16
Torque current
6
23
M09
M09
17
Output frequency
5
24
M10
M10
18
Motor output
5
25
M11
M11
19
Output current (rms)
5
26
M12
M12 1A
Output voltage (rms)
3
27
M13
M13 1B
RUN command, Di, RESET input (final)
14
28
M14
M14 1C
Operation state
16