MAN0373-01 13 APR 2000 PAGE 35

CH.5

Data format [14]: Operation command

RST

0

0

0

0

X9

X8

X7

X6

X5

X4

X3

X2

X1

REV

FWD

Not yet used Multi-function command

FWD: Forward rotation Command

REV: Reverse rotation Command

(All bit are ON by 1)
Example) If S06 (operation command) = FWD, X1 and X5 = ON

Since 0000 0000 0100 0101

b

= 0045

H

Data format [15]: Universal output terminal

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

Y5

Y4

Y3

Y2

Y1

Not yet used

Universal output

(All bit are ON by 1)

Example) If M15 (Universal output terminal)=Y1 and Y5 = ON

Since 0000 0000 0001 0001

b

= 0011

H

Data format [16]: Operating state

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

BUSY

WR

RL

ALM DEC ACC

IL

VL

TL

NUV BRK

INT

EXT REV FWD

(All bit are ON or active by 1)

FWD:

Under forward operation

IL:

Under current limiting

REV:

Under reverse operation

ACC:

Under acceleration

DEC:

Under deceleration

EXT:

Under DC braking (or under
pre-excitation)

ALM:

Lump alarm

INT:

Inverter trip

RL:

Transmission valid

BRK:

Under braking

Function writing right
0: Keypad panel

NUV:

DC link voltage is established
(undervoltage at 0)

1: RS485

TL:

Under torque limiting

WR:

2: Link (option)

VL:

Under voltage limiting

BUSY:

Under data writing (processing)

Alarm

reset

Advertising