GE Industrial Solutions HE300GEN150 User Manual
Page 34
MAN0373-01 13 APR 2000 PAGE 35
CH.5
Data format [14]: Operation command
RST
0
0
0
0
X9
X8
X7
X6
X5
X4
X3
X2
X1
REV
FWD
Not yet used Multi-function command
FWD: Forward rotation Command
REV: Reverse rotation Command
(All bit are ON by 1)
Example) If S06 (operation command) = FWD, X1 and X5 = ON
Since 0000 0000 0100 0101
b
= 0045
H
Data format [15]: Universal output terminal
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
0
0
0
Y5
Y4
Y3
Y2
Y1
Not yet used
Universal output
(All bit are ON by 1)
Example) If M15 (Universal output terminal)=Y1 and Y5 = ON
Since 0000 0000 0001 0001
b
= 0011
H
Data format [16]: Operating state
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
BUSY
WR
RL
ALM DEC ACC
IL
VL
TL
NUV BRK
INT
EXT REV FWD
(All bit are ON or active by 1)
FWD:
Under forward operation
IL:
Under current limiting
REV:
Under reverse operation
ACC:
Under acceleration
DEC:
Under deceleration
EXT:
Under DC braking (or under
pre-excitation)
ALM:
Lump alarm
INT:
Inverter trip
RL:
Transmission valid
BRK:
Under braking
Function writing right
0: Keypad panel
NUV:
DC link voltage is established
(undervoltage at 0)
1: RS485
TL:
Under torque limiting
WR:
2: Link (option)
VL:
Under voltage limiting
BUSY:
Under data writing (processing)
Alarm
reset