PAGE 32 13 APR 2000 MAN0373-01
CH. 5

5.2

Data Format Specification

Data format [1]:

Integer data (Positive): Min. unit 1

Example) If F15 (Frequency limiter, upper limit)= 60Hz

Since 60 = 003C

H

Data format [2]: Integer data (Positive, negative): Min. unit 1

Example) -20

Since -20 = FFEC

H

Data format [3]: Decimal data (Positive): Min. unit 0.1

Example) If F17 (gain frequency setting signal) = 100.0%

Since 100.0

×

10 = 1000 = 03E8

H

Data format [4]: Decimal data (Positive, negative): Min. unit 0.1

Example) If C31 (Analog input offset adjust, terminal12) = - 5.0%

Since - 5.0

×

10= - 50 = FFCE

H

Data format [5]: Decimal data (Positive): Min. unit 0.01

Example) If C05 (multi-step frequency 1) = 50.25Hz

Since 50.25

×

100 = 5025 = 13A1

H

Data format [6]: Decimal data (Positive, negative): Min. unit 0.01

Example) If M07 (actual torque value)= - 85.38%

Since - 85.38

×

100= - 8538=DEA6

H

Data format [7]: Decimal data (Positive): Min. unit 0.001

Example) If o05 (follow - up side ASR 1 constant) = 0.105s

Since 0.105

×

1000 = 105 = 0069

H

Data format [8]: Decimal data (Positive, negative): Min. unit 0.001

Example) If being -1.234

Since - 1.234

×

1000 = - 1234 = FB2E

H

Data format [9]: Integral data (Positive): Min. unit 2

Example) If P01 (Motor 1 number of poles) =2pole

Since 2 = 0002

H