PAGE 36 13 APR 2000 MAN0373-01
CH. 5

Data format [17]: Type code

Type

Generation

Series

Voltage series

Code

Type

Generation

Series

Voltage series

1

VG

G11/P11

For domestic

100V single phase

2

G

-

For Asia

200V single phase

3

P

-

For China

200V three phase

4

E

-

For Europe

400V three phase

5

C

-

For USA

575V three phase

6

S

-

-

-

Data format [18]: Code setting

Data 4

Data 3

Data 2

Data 1

Example) If o22 (Ai function selection)=123

Since 123=0123

H

Data format [19]: Amperage value Decimal data (positive):

Min. unit 0.01 for inverter capacity is not more than 30HP
Min. unit 0.01 for not less than 40HP respectively

Example) If F11 (electronics thermal overload relay 1 level)107.0A (40HP)

Since 107.0

×

10=1070=042E

H

If F11 (electronics thermal overload relay 1 level)=3.60A (1HP)

Since 3.60

×

100=360=0168

H

Data format [20] Transmission error code

Code

Description

Code

Description

1

FC (function code) error

71

CRC error

(no response)

2

Illegal address

72

Parity error

(no response)

3

Illegal data (Data range error)

7

NAK

- Priority for link
- No right for writing error
- Forbidden writing error

73

Other errors

(no response)

- Framing error
- Overrun error
- Bufferfull error

Example) If illegal address

Since 2=0002

H