MAN0373-01 13 APR 2000 PAGE 41

CH. 6

The starting address for the COMM_REQ is the first word in the first block move at %R100. Table 6.1 provides
an explanation of the values in the example (Figure 6.1) that are either specific to the drive or change depending
on the COMM_REQ values. The values in the example are bold and are noted by superscript numbers that
correlate to the numbers in Table 6.1

Table 6.1 – Superscript Notes (Ladder #1 Example)

Superscript

Number

COMM_REQ

Location

Name

Description

1

Address

Command Length

Number of words from Address+6 to
Address+n

2

Address+7

Device Number

Device to receive COMM_REQ; 0-31,
or 255 to broadcast

3

Address+11

Datagram Length

(Bytes)

Length of datagram content beginning
at Address+12

4

Address+12

Starting Parameter

Number

(High byte)

High byte of word contains starting
drive parameter.

5

Address+14

Number of Parameter

Values to Write

(High byte)

High byte of word contains number of
parameter values, in bytes, to write to
the drive.

6

Address+15 to

Address+n

Parameter Value

Value(s) to be written sequentially to
drive starting with the parameter
number at Address+12 and ending
with the parameter number + number
of parameters.

Advertising