Events (alarms and messages)

Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software “GE Data Protection” installed or with the monitoring system “GE Power Diagnostic”.


Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED Alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the acoustical alarm).

Code

Alarms

Meaning

4608

The propagation of the IEMi Operation Mode configuration
to other units in a Parallel System failed.

ECO CONFIG FAILURE



Code

Message

Meaning

4604

COMMAND IEMi ON

The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will run in
IEMi Operation Mode.

4605

COMMAND IEMi OFF

The IEMi Operation Mode has been disabled or the
programmed time is expired.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.

4606

eBoost/IEMi ACTIVATION

ALLOWED

IEMi control signal has been cleared on the Customer
Interface Board
(X1 - 11, 22).
Operating mode depends on scheduled activation of the
functions.

4607

eBoost/IEMi ACTIVATION

INHIBITED

Customer Interface Board (X1 - 11, 22) received an IEMi
control
signal.
IEMi Operation Mode will be temporarily inhibited.

Modifications reserved

Page 11/24

OPM_OPT_IEM_iXX_XXX_XGB_V010.doc

User Manual IEMi - Intelligent Energy Management integrated