To better understand the IEMi programming modes, some typical examples are shown:
Example 1:
For continuous IEMi Operation Mode set the IEMi START times to 00:00 and the IEMi STOP times to
23:59 for all weekdays, but almost 1 day must have 1 minute of VFI programmation: i.e d2 - Sunday
00:00 to 23:58).
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
IEMi START
00:00 00:00 00:00 00:00 00:00 00:00 00:00
IEMi STOP
23:59 23:58 23:59 23:59 23:59 23:59 23:59
Example 2:
IEMi STOP before IEMi START.
IEMi START 18:00, IEMi STOP 06:00 for weekday d4 - Tuesday.
Means that on d4 - Tuesday the IEMi Operation Mode is active between 00:00 and 06:00 and between
18:00 and 23:59.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
IEMi START
00:00 00:00 00:00 18:00 00:00 00:00 00:00
IEMi STOP
23:59 23:59 23:59 06:00 23:59 23:59 23:59
Example 3:
IEMi Operation Mode during the night and week-end.
If the IEMi Operation Mode must be enabled all nights (d3 - Monday ÷ d7 - Friday) between 18:00 in the
evening and 06:00 of the following morning and during all Saturday (d1) and Sunday (d2), the
corresponding parameters are:
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
IEMi START
00:00 00:00 18:00 18:00 18:00 18:00 18:00
IEMi STOP
23:59 23:59 06:00 06:00 06:00 06:00 06:00
Example 4:
If the IEMi Operation Mode must be enabled on Monday (d3) and Tuesday (d4) between 18:00 in the
evening and 06:00 of the following morning, on Friday (d7) between 12:00 and 13:00, during all Saturday
(d1) and on Sunday (d2) until 20:00, the corresponding parameters are.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
IEMi START
00:00 00:00 18:00 18:00 00:00 00:00 12:00
IEMi STOP
23:59 20:00 23:59 06:00 06:00 00:00 13:00
IEMi START
IEMi STOP
In dark color are displayed the times with IEMi Operation Mode.
The arrows indicate the conditions given by the IEMi START and IEMi STOP times introduced with the
parameters.
Note that on day d6 - Thursday the interval has length 0 (zero), therefore the IEMi Operation Mode is not
enabled on this day.
Modifications reserved
Page 14/24
OPM_OPT_IEM_iXX_XXX_XGB_V010.doc