3.2.2 Alarms

The alarms mode is entered any time the

alarms button is pressed.
The LCD will display a series of screens
corresponding to the last 256 events, one event
per screen.


The buttons perform the following functions:

metering Abandons

alarms mode and enters metering mode.

alarms Next

screen.

parameters Abandons

the

alarms mode and enters the parameters mode.

+

Scrolls forward to the next screen.

Scrolls backward to the previous screen.

ok

Display the main screen for this mode.

01.01.2006 12:45:07
NR=255 Status=4A61

4115: LOW

BATTERY VOLTAGE

metering

alarms

parameters

+

ok

The information displayed includes:

The exact date and time when the event occurred.

The number of the event, 255 being the most

recent event, and 0 the oldest.

The standard GE code for the event and the
machine status word.

An explicit text description of the event.

Events (alarms and messages)

Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED Alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the acoustical alarm).

Code

Alarms

Meaning

4608

The propagation of the IEMi Operation Mode configuration
to other units in a Parallel System failed.

ECO CONFIG FAILURE

Code

Message

Meaning

4604

COMMAND IEMi ON

The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will run in
IEMi Operation Mode.

4605

COMMAND IEMi OFF

The IEMi Operation Mode has been disabled or the
programmed time is expired.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.

4606

IEMi ACTIVATION ALLOWED

IEMi control signal has been cleared on the Customer
Interface Board
(X1 - 11, 22).
IEMi Operation Mode depends on scheduled activation of
the functions.

4607

IEMi ACTIVATION INHIBITED

Customer Interface Board (X1 - 11, 22) received an IEMi
control
signal.
IEMi Operation Mode will be temporarily inhibited.

Modifications reserved

Page 19/24

OPM_OPT_IEM_iXX_XXX_XGB_V010.doc

User Manual IEMi - Intelligent Energy Management integrated

Advertising