2 customer interface im0171, 3 3-ph snmp/web adapter, Customer interface im0171 – GE Industrial Solutions IEMi User Manual

Page 24: Ph snmp/web adapter, X1 x2 j1

Advertising
background image

6.2 CUSTOMER INTERFACE IM0171

X1 terminals – Output signals on voltage free contacts

X1 / 1, 2, 3

NO, C, NC

Mains Failure

(def. Parameter RL=1)

X1 / 4, 5, 6

NO, C, NC

Load on Inverter

(def. Parameter RL=3)

X1 / 7, 8, 9

NO, C, NC

Stop Operation

(def. Parameter RL=5)

X1 / 12, 13, 14

NO, C, NC

Load on Mains

(def. Parameter RL=2)

X1 / 15, 16, 17

NO, C, NC

General Alarm

(def. Parameter RL=4)

X1 / 18, 19, 20

(def. Parameter RL=6)

NO, C, NC

Acoustic Alarm

The programmable signals on X1 will be disabled with Q1 open,
with the exception of the signals for “16 - Manual Bypass ON”

and “26 - EPO”
.

Input contacts

X1 / 10, 21

NO Programmable

12

8

19

21
22

20

10
11

9

17
18

16

15

7

6

5

4

12

14

13

3

2

1

X1

X2

J1

SGSE

_600_

S1_

Cus

to

m

er

int

erfa

ce_0

1

X1 / 11, 22

NO

Programmable / Generator ON

Fig. 7.2-1 Customer Interface IM0171


On terminals X1 connector, the output signals can be associated to a specific function.
This selection can be performed from the display by QUALIFIED AND TRAINED PERSONNEL (password
required).

With reference to IEMi Operation Mode, the following function is available:

27- eBoost/IEMi mode.
This signal indicates when IEMi Operation Mode is enabled and active.



Some UPS functions can be activated when an external Normally Open contact is closed on:

X1-10, 21 or X1-11, 22
The specific function can be selected from the display by QUALIFIED AND TRAINED PERSONNEL
(password required).

With reference to IEMi Operation Mode, the following function is available:

8 – eBoost/IEMi control.
When active, this function will deactivate IEMi Operation Mode.




6.3 3-PH SNMP/WEB ADAPTER

IEMi Operation Mode can be enabled, disabled and programmed via the web interface of a 3-ph
SNMP/Web adapter
when this option is available in the Parallel System.
The configuration selection mirrors the parameters described in this manual.
For further details, refer to the product documentation of the 3-ph SNMP/Web adapter option.

Modifications reserved

Page 24/24

OPM_OPT_IEM_iXX_XXX_XGB_V010.doc

User Manual IEMi - Intelligent Energy Management integrated

Advertising