GE Industrial Solutions IEMi User Manual
Page 15
Example 5:
An equivalent set of parameters for Example 4 is.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
IEMi START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
IEMi STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
IEMi START
IEMi STOP
The IEMi Operation Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 -
Tuesday (as indicated by the IEMi STOP time of weekday d4 - Tuesday).
The IEMi STOP time of weekday d3 - Monday has no effect as it is followed by the IEMi STOP time of
weekday d4 - Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the IEMi Operation Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of weekday
d5 - Wednesday.
The IEMi START time of weekday d5 - Wednesday has no effect as it is preceded by the IEMi START time
of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired IEMi Operation Mode, verify:
• Date and Time (first page of parameter).
• IEMi Operation Mode screen shows how many hours of IEMi Operation Mode have
been selected for each day of the week.
NOTE !
For IEMi Operation Mode to become active a manual Inverter start is required at
start-up and after a Load Off reset.
Modifications reserved
Page 15/24
OPM_OPT_IEM_iXX_XXX_XGB_V010.doc
User Manual IEMi - Intelligent Energy Management integrated