4 inputs, 5 communications, 6 physical – GE Industrial Solutions EPM4500 Submeter User Manual

Page 10: 7 type tests and approvals, Nputs, Ommunications, Hysical, Ests, Pprovals

Advertising
background image

1–6

EPM 4500 SUB METER – INSTRUCTION MANUAL

SPECIFICATIONS

CHAPTER 1: OVERVIEW

1.3.4

Inputs

AC CURRENT INPUTS

CT input:..............................................................50 to 800 A primary available
Secondary inputs: ..........................................0.1 A or 5 A

AC VOLTAGE INPUTS
Metered voltage:.............................................120/208 V wye, 277/480 V wye, or 600 V delta

at 50 to 60 Hz

Rated voltage:..................................................90 to 110%

PULSE INPUTS
Inputs:..................................................................up to 48 form-A pulse inputs logged in programmable

intervals also count during power outage

Minimum wire gauge:...................................20 AWG
Maximum wire length: .................................300 ft.
Maximum rate: ................................................5 transitions/second
Minimum pulse width:..................................100 ms

1.3.5

Communications

EPM4

500 COMMUNICATIONS

Protocols:............................................................Power line communications (PLC)

RS485 Modbus (2-wire, half-duplex, isolated)

Ports: ....................................................................IEC front optical point-of-access (POA) port

1.3.6

Physical

ENVIRONMENT
Usage:..................................................................For indoor use only
Enclosure:...........................................................NEMA 1 rated
Temperature:....................................................–20°C to +60°C
Humidity:............................................................0 to 95% relative humidity (non-condensing)
Pollution degree:.............................................1
Maximum altitude:.........................................2000 m

DIMENSIONS

Meter enclosure:.............................................13.5"H

× 8.5"W × 4.5"D

CT terminal board enclosure: 13.5"H

× 8.5"W × 4.5"D

SHIPPING
Shipping weight: .............................................1 meter assembly 34 lbs. (total weight)
Shipping dimensions: ...................................2 enclosures, each 13.5"H

× 8.5"W × 4.5"D

1.3.7

Type Tests and Approvals

TYPE TESTS
Transient/surge suppression: ANSI C37.90.1-1989
Installation category:....................................III. This product falls under Installation Category III

because of its distribution level, fixed installation and has
smaller transient overvoltages than an Installation
Category IV.

Advertising