3 confirming connection to the epm4500, 4 logging into the meter, Onfirming – GE Industrial Solutions EPM4500 Submeter User Manual

Page 48: Onnection, Epm4500 -6, Ogging, Into, Eter

Advertising
background image

4–6

EPM 4500 SUB METER – INSTRUCTION MANUAL

MODBUS ACTIVATION

CHAPTER 4: COMMUNICATIONS

Z

Select the File > Properties > Settings > ASCII Setup menu item.
Check the Echo typed characters locally option, as shown below.

4.2.3

Confirming Connection to the EPM4

500

To confirm a proper RS485 connection to the EPM4500, enter the following command:

attn -D

(followed by the [ENTER] key)

If meter is properly connected, it will respond with a serial number and poll address. Once
in Modbus mode, this command will no longer work.

For example, entering the command

attn -D

followed by the [ENTER] key returns:

60005866 256

for a meter with serial number 60005866 and poll address 256.

4.2.4

Logging into the Meter

Use the following procedure to login to the EPM4500.

Z

Setup a ‘key macro’ in HyperTerminal by selecting the View > Key
Macros
menu item.

Z

Click New and select an appropriate macro key sequence (ALT-1 is
used the example below.

Z

Enter the following command in the Action area:

attn -S[serialNumber] -5lEvElbAl<ENTER>

Z

The password is -s5 followed by the LABLEVEL text spelled
backwards, with the vowels in upper case.
This login string must be followed by the ENTER command within
the key macro.

For example, for a unit with serial number 60005866, enter the following text: