EPM 4500 SUB METER – INSTRUCTION MANUAL

MODBUS COMMUNICATIONS

CHAPTER 4: COMMUNICATIONS

FIGURE 4–1: RS-485 Serial Connections

Note

The EPM4500 optical port is disabled for units with 2-wire RS485 connections.

4.1.2

RS232 Wiring for Modbus

The wiring for Modbus communications for RS232 is indicated below.

4.1.3

Modbus Commands

The EPM4500 is capable of acting as a remote slave unit to a Modbus master device via
modem, RS232, RS485, or PLC. Up to 32 EPM4500 meters (or other RS485 devices) can be
daisy-chained together on a single LAN.

The EPM4500 communicates at a default baud rate of 19200, with no parity and 1 stop bit.
The default Modbus address is 100. Changes to the default baud rate or address can be
accomplished through the configuration file upload.

The following Modbus commands are supported by the EPM4500:

• 03: Read R4 type register(s)
• 06: Write single register; address “0” is used as the broadcast address
• 16: Write multiple registers; address “0” is used as the broadcast address

4.1.4

Fixed Modbus Values

The EPM4500 provides fixed register values indicating the meter's serial number, the
meter's version number, and the Modbus addresses.

709725A1.CDR

Color

Function

DB-9 Pinout

Black

TX

2

Red

RX

3

Green

GND

5