GE Industrial Solutions EPM4500 Submeter User Manual

Page 52

Advertising
background image

4–10

EPM 4500 SUB METER – INSTRUCTION MANUAL

MODBUS MEMORY MAP

CHAPTER 4: COMMUNICATIONS

003A

0058

Date/Time of Oldest Interval - Hours/Minutes

R

Hours/Minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

003B

0059

Date/Time of Oldest Interval - Month/Day

R

Month/Day

16-bit

Month: 1=Jan., 12=Dec. (bitmask = FF00)

Day: 1-31 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

003C

0060

Date/Time of Oldest Interval - Year

R

Year

16-bit Unsigned Integer

003D

0061

Date/Time of Newest Interval - Hours/Minutes

R

Hours/Minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF)

003E

0062

Date/Time of Newest Interval - Month/Day

R

Month/Day

16-bit

Month: 1=Jan., 12=Dec. (bitmask = FF00)

Day: 1-31 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

003F

0063

Date/Time of Newest Interval - Year

R

Year

16 Bit Unsigned Integer

0040

0064

Date/Time of Currently Selected Interval - Hours/

Minutes

RW Hours/Minutes

16-bit, Hours: 0-23 (bitmask = FF00)

Minutes: 0-59 (bitmask = 00FF

0041

0065

Date/Time of Currently Selected Interval - Month/Day RW Month/Day

16-bit

Month: 1=Jan., 12=Dec. (bitmask = FF00)

Day: 1-31 (bitmask = 00FF)

DDE Data is COM Compatible,

Date/Time Numeric

0042

0066

Date/Time of Currently Selected Interval - Year

RW Year

16 Bit Unsigned Integer

0043

0067

Data Ready Flag

RW

16 Bits: Mask out/ignore Bit 15.

0=Data is ready for read

1=Populate registers with timestamp data

2=Invalid Timestamp Requested

Stored Dynamic Data Ready for Read

Average Interval Data

0063

0099

Interval Data Qualifying Register

R

16-bit Unsigned Integer, 8 = Invalid Interval

0064

*

0100

Meter #1 Three-Phase Total kW

R

kW

Stored Interval 1 for Meter #1

0066*

0102

Meter #1 Three-Phase Total kvar

R

kvar

Stored Interval 2 for Meter #1

0068*

0104

Meter #1 Three-Phase Total kVA

R

kVA

Stored Interval 3 for Meter #1

006A*

0106

Meter #1 Three-Phase Total Power Factor

R

%

Stored Interval 4 for Meter #1

006C*

0108

Meter #2 Three-Phase Total kW

R

kW

Stored Interval 1 for Meter #2

006E*

0110

Meter #2 Three-Phase Total kvar

R

kvar

Stored Interval 2 for Meter #2

0070*

0112

Meter #2 Three-Phase Total kVA

R

kVA

Stored Interval 3 for Meter #2

0072*

0114

Meter #2 Three-Phase Total Power Factor

R

%

Stored Interval 4 for Meter #2

0074*

0116

Meter #3 Three-Phase Total kW

R

kW

Stored Interval 1 for Meter #3

0076*

0118

Meter #3 Three-Phase Total kvar

R

kvar

Stored Interval 2 for Meter #3

0078*

0120

Meter #3 Three-Phase Total kVA

R

kVA

Stored Interval 3 for Meter #3

007A*

0122

Meter #3 Three-Phase Total Power Factor

R

%

Stored Interval 4 for Meter #3

007C*

0124

Meter #4 Three-Phase Total kW

R

kW

Stored Interval 1 for Meter #4

007E*

0126

Meter #4 Three-Phase Total kvar

R

kvar

Stored Interval 2 for Meter #4

0080*

0128

Meter #4 Three-Phase Total kVA

R

kVA

Stored Interval 3 for Meter #4

Table 4–1: Modbus Memory Map (Sheet 2 of 15)

Hex

Addr

Addr

Description

R/W

Units

Notes

Advertising