CHAPTER 4: COMMUNICATIONS

MODBUS MEMORY MAP

EPM 4500 SUB METER – INSTRUCTION MANUAL

4–23

Note

1.

32-bit floating point numbers are as per the IEEE 754-1985 standard.

2.

Registers 0X0063 to 0X025E are all read-only and cannot be modified. They break
down as follows:

Registers 0X0064 to 0X0122 are not real-time, but are populated with
stored interval data based on user inputs to registers 0X0040 to 0X0043.

Registers 0X0162 to 0X025E are all real-time data registers.

0468*

1128

Meter #8 Phase Angle A

R

degrees

Meter #8 Phase Angle

046A*

1130

Meter #8 Phase-to-Phase Voltage A

R

V

Meter #8 Instantaneous Voltage

046C*

1132

Meter #8 THD Phase B

R

%

Meter #8 Total Harmonic Distortion

046E*

1134

Meter #8 Phase Angle B

R

degrees

Meter #8 Phase Angle

0470*

1136

Meter #8 Phase-to-Phase Voltage B

R

V

Meter #8 Instantaneous Voltage

0472*

1138

Meter #8 THD Phase C

R

%

Meter #8 Total Harmonic Distortion

0474*

1140

Meter #8 Phase Angle C

R

degrees

Meter #8 Phase Angle

0476*

1142

Meter #8 Phase-to-Phase Voltage C

R

V

Meter #8 Instantaneous Voltage

Counters

07D0

2000

Number of phases offset

R

16-bit Unsigned Integer

1, 2, 3, or 24 phases available

07D1

2001

Demand Window Offset

R

16-bit Unsigned Integer

5, 15, or 30 minutes available

07D2

2002

I Multiplier Type Offset

R

16-bit Unsigned Integer

Internal calibration value

07D3

2003

Number of Pulse Counters Offset

R

16-bit Unsigned Integer

Number of external pulse inputs installed

07D4

2004

Overlap Offset

R

16-bit Unsigned Integer

Number of adjacent demand windows that are averaged

to determine peak demand

07D5

2005

Number TOU's Offset

R

16-bit Unsigned Integer

Number of different TOU periods defined in the time-of-

use table

07D6

2006

MDT_M_TABLE_REG_START

R

16-bit Unsigned Integer

07D7

2007

NUM_MDT_M_TABLE_COLUMNS

R

16-bit Unsigned Integer

07D8

2008

NUM_MDT_M_TABLE_REGS

R

16-bit Unsigned Integer

07D9

2009

MDT_M_TABLE_REG_END

R

16-bit Unsigned Integer

* 32-bit floating point register.

+

32-bit long integer - Range: 00000000h to FFFFFFFFh

Table 4–1: Modbus Memory Map (Sheet 15 of 15)

Hex

Addr

Addr

Description

R/W

Units

Notes