CHAPTER 1: OVERVIEW

SPECIFICATIONS

EPM 4500 SUB METER – INSTRUCTION MANUAL

1–5

1.3

Specifications

1.3.1

Monitoring

DEMAND
Consumption and demand: .....................kW and kWh
Demand reset: .................................................allows local reset of peak demand register

INTERVAL DATA AND PEAK DEMAND
Commercial:......................................................15 minute block demand interval and peak demand with

date and time stamp

Residential:........................................................1 hour block demand interval

DATA LOGGER
Duration:.............................................................120 days with kW and kWh
Battery:................................................................internal battery maintains time and current interval

metering data during power outage only

1.3.2

Power Supply

CONTROL POWER
Input: ....................................................................120 V phase A to neutral

277 V phase A to neutral
480 V phase to phase
(internally powered through metered voltage; no external
source is required)

Frequency:.........................................................50 to 60 Hz
Operating power: ...........................................2 watts for 120 V

5 watts for 277 V and 480 V

Fuses:...................................................................1 - Buss fuse 250 V / 500 V 0.25 A / 0.125 A slow-acting

3 - Buss fuse 250 V /600 V 4.0 A fast-acting

1.3.3

Metering

MEASURED VALUES
Real time per phase:.....................................voltage, current, kW, kvar, kVA, power factor, frequency,

phase angle

Data logging:....................................................kWh, kW demand

METER ACCURACY
Accuracy: ...........................................................0.5 class accuracy

±0.5% unity and 50% power factor, 1 to 100% of full-
scale

Standards: .........................................................meets revenue certifiable ANSI C12.1 and C12.16

accuracy standards

LIQUID CRYSTAL DISPLAY (LCD)
Display size:.......................................................32-digit LCD, 16 digits in two rows
Data digit height:............................................0.31"
Consumption register: .................................6 digits

Advertising