Troubleshooting, Led codes, Operation troubleshooting – Bell & Gossett 6 71 075 141B ecocirc wireless Potable Hot Water Recirculation Kit User Manual

Page 23: Led codes operation troubleshooting

Advertising
background image

Troubleshooting

LED codes

Pump LED sequence code

Explanation

No light

Pump is off — no power

Steady light on LED

Pump is running or on stand-by

One short and one long flash

Low input voltage to pump

Two short and one long flash

Communication is lost between pump and valve

Three short and one long flash

Pump is overheated

Four short and one long flash

Pump is overloaded

Five short and one long flash

Blocked rotor inside pump

Six short and one long flash

Low battery voltage at the valve

Short fast flashes

Pump is in pairing mode

Repeater / push-button LED sequence code

Explanation

Steady light

System is running

Seldom flashes

System is running

Short fast flashes

Push-button / signal repeater is in pairing mode

Operation troubleshooting

Symptom

Cause

Remedy

Pump does not turn on

Timer slide switch is set to “OFF”

position or timer clock is not

programmed to allow operation.

Set the slide switch to the “ON”

position or program the timer

clock.

Water at the valve is already at

the set temperature and does not

require pump operation.

Pump will turn on when the

water at the valve cools. Verify

the temperature setting on the

pump.

Outlet has no power

Check that there is power at the

outlet. Make sure the outlet that

the pump is plugged into is not

controlled by a wall switch.

GFCI is tripped.

Verify the “TEST” and “RESET” of

the GFCI outlet that the pump is

plugged into.

Troubleshooting

Bell & Gossett ecocirc

®

wireless Potable Hot Water Recirculation Kit Instruction

Manual

21