Vent Terminal

Clearance

A=

Above grade, veranda, porch, deck,
or balcony

B=

Window or door that may be opened

12" (36")

C=

Permanently closed window

D=

Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet from the
center of the terminal

*

E=

Unventilated soffit

*

F=

Outside corner

*

G=

Inside corner

*

H=

Each side of center line extended
above meter/regulator assembly

3' within a height 15' above
meter/regulator assembly

I=

Service regulator vent outlet

3'

J=

Nonmechanical air supply inlet or
combustion air inlet to any other
appliance

12" (36")

K=

Mechanical air supply inlet

3' above if within 10' (6')

L=

Above paved sidewalk or paved
driveway located on public property
Under veranda, porch, deck, or
balcony

(7' ***)

M=

()= indicates clearances required in Canada
*Maintain clearances in accordance with local installation codes and the requirements of the gas supplier
***A vent shall not terminate directly above a sidewalk or paved driveway that is located between two
single family dwellings and serves both dwellings.
****Permitted only if veranda,porch,deck,or balcony is fully open on a minimum of two sides beneath the floor.

* (12"- Canada Only****)

*

12" (12")

Air Supply Inlet

Area Where Terminal
is Not Permitted

Clearance Requirements from Vent Terminations to Building Openings

* All clearance requirements are in accordance with ANSI Z21.10.3a-2003 and the National Fuel Gas

Code, ANSI Z223.1.