Vent terminal installation precautions
Note the following vent terminal installation

requirements.

1) Do not install the vent terminal indoors

2) Install the vent terminal with a downward slope

3) Install with the proper length protruding through the wall

4) Avoid installing the terminal where obstacles will block it

• This restriction will not be applied to an area

where an effective shield makes a clearance of
24" or more in front of the exhaust outlet.

Above

There must be a
clearance of 24" or
more in front of the
vent terminal.

Vent terminal

3.

Installation Requirements

Caution

sloping
up

sloping
down

The red line is
not visible.

Distance A

24" or more

12" or more

If the front wall is
flammable.
If the front wall is
nonflammable.

Vent terminal

Vent terminal

12" or more

12" or more

12" or more

Vent terminal

12" or more

Sides

Below

Vent terminal

12" or more

Vent terminal

A

Front

Vent terminal

Vent terminal

12" or more

12" or more

12" or more 12" or more

12" or more

There must be no
building opening
within this area.

Flue terminal

Vent Terminal Clearance Requirements

Clearances from obstacles Clearances from combustibles

Clearances from combustibles

not far
enough

too far

The red rectangle
is visible.

Proper installation. The
red line is visible, but the
red rectangle in not
visible from the outdoors

Snow
drift

Tree

Gasoline

Gas

Clearance between two terminals

Vent
terminal