Serial communications, cont’d – Extron Electronics TPS150 User Guide User Manual

Page 32

Advertising
background image

Serial Communications, cont’d

TPS150 Switching and Transmission System • Serial Communications

4-4

The transmitter’s serial port is factory-configured to 9600 baud, no parity, no
flow control, half-duplex mode. If desired, the computer’s serial port settings
can be changed from within the ICS100 program.

2

.

Click Communications > Comm Port > Comm 1 (or the correct Comm port). The
Serial Port setup window appears (figure 4-3).

Figure 4-3 — Serial Port setup window

3

.

Click in the appropriate radio buttons to select the desired settings for the
computer connected to the transmitter.

4

.

Click OK.

5

.

Click Inline Model > Select Address. The Addresses window (figure 4-4)
appears.

Figure 4-4 — Addresses window

The transmitter must be addressed before it will accept and respond to
commands. The addressing operation routes setup information to a particular
unit on a network and enables command responses. Once the transmitter is
addressed, it can accept an unlimited number of commands. If a different unit
is addressed, the TPS150 ignores subsequent commands until it is addressed
again.

The factory-installed default address is 97, but this number can be changed.
The transmitter can also take commands after receiving a broadcast address of
00, but it does not send responses. Broadcast addressing is for multiple units
on a network serial line in half-duplex mode.

6

.

Click and drag on the slider or click the scroll up ( ) or scroll down ( )
button until the desired address is visible.

7

.

Click on the desired address. The default address is 97.

8

.

Click OK.

Advertising