Mechanical data 6.5. electrical data – Burkert Type 8791 User Manual

Page 10

Advertising
background image

10

Technical data

Environmental
temperature

0 to +60 °C

Protection class

IP65 / IP67

1)

according to EN 60529

(only if cables, plugs and sockets have
been connected correctly)

1)

If the positioner is used under IP67 conditions, the ventilation
filter (see “Fig. 1”) must be removed and the exhaust air
conducted into the dry area.

6.4. mechanical data

Dimensions

See data sheet

Material

Housing material

Plastic-coated aluminium

Other external parts

Stainless steel (V4A), PC, PE, POM, PTFE

Sealing material

EPDM, NBR, FKM

Weight

approx. 1.0 kg

6.5. electrical data

Connections

2 cable glands (M20 x 1.5) with screw-
type terminals 0.14 – 1.5 mm

2

or circular

plug-in connector (M12, 8 pole plug)

Interfaces

Communications interface USB:
Direct connection to PC via USB adapter.
Communication with communications
software based on FDT/DTM technology.
An external adapter with integrated
interface driver is required.

Supply voltage

24 V DC ± 10 %, max. residual ripple 10%

Power consumption

< 3.5 W

Input resistance for

set-point value signal

180 Ω in 0/4 - 20 mA / Resolution 12 bit

Protection class

3 in accordance with VDE 0580

Analog position feedback

max. Burden (load)
for current output
0/4 – 20 mA)

560 Ω

Inductive proximity
switches

100 mA current limit

Binary input

Not galvanically isolated
0 – 5 V = log “0”, 10 – 30 V = log “1”
inverted input in reverse order
(input current < 6 mA)

english

Type 8791

Advertising