Burkert Type 8791 User Manual

Page 14

Advertising
background image

14

Operating

7.2.2. function of the Dip switches

on

1 2 3 4

DiP-
Switches

Position Function

1

ON

Reversal of the effective direction of the
set-point value (

DIR.CMD)

(set-point value 20 – 4 mA corresponds to
position 0 – 100%)

OFF

Normal effective direction of the set-point
value (set-point value 4 – 20 mA corre-
sponds to position 0 – 100%)

2

ON

Sealing function active.
The valve completely closes below 2%

5)

and opens above 98% of the set-point
value (

CUTOFF)

OFF

No sealing function

DiP-
Switches

Position Function

3

ON

Correction characteristic for adjustment of
the operating characteristic (Linearization of
the operating characteristic

CHARACT)

6)

OFF

Linear characteristic

4

ON

MANUAL operating status

OFF

AUTO AUTOMATIC operating status

5)

Factory setting can be changed via communications software.

6)

Characteristic type can be changed via communications
software.

Tab. 3: Function of the DIP switches

information about the communications software:
The switching position of the DIP switch has priority over
the communications software!
If the values of the sealing function (

CUTOFF) or the cor-

rection characteristic (

CHARACT) are changed via the

software tool, the corresponding function must be active
(DIP switch set to ON).
The effective direction of the set-point value (

DIR.CMD) can

be changed via the DIP switches.

english