Error messages – Burkert Type 8791 User Manual

Page 16

Advertising
background image

16

Operating

7.3. error messages

7.3.1. error messages in manual and

auTomaTic operating status

Display Cause of fault

remedial
action

LED 3
(red,
FAULT)
on

Checksum error in data memory
→ Data memory defective
→ The device automatically switches

to an older (possibly not current)
data record.

not pos-
sible, device
defective.
Contact your
Bürkert sales
office.

Tab. 6: Error messages in MANUAL and AUTOMATIC operating status

7.3.2. error messages while the X.TUNE

function is running

Display Cause of fault

remedial action

LED 3
(red,
FAULT)
on

No compressed air
connected

Connect compressed air

Compressed air failure
during the

X.TUNE

Check compressed air
supply

Actuator or control
system deaeration side
leaking

not possible, device
defective

Control system aeration
side leaking

not possible, device
defective

The angular range of the
position sensor exceeds
180°

Correct the attachment of
the shaft for the position
sensor on the actuator (see
chapter “8.2.1” and “8.3.1”).

Tab. 7: Error messages while the X.TUNE function is running

english

Type 8791