Fluid connection

for double-acting actuators (control function i):

Connect working connections A1 and A2 to the respective
chambers of the double-acting actuator.
Safety positions see chapter “9.3. Safety positions”.

important information for perfect control behaviour!
This ensures that the control behaviour is not extremely
negatively affected in the upper stroke range on account of
too little pressure difference.
• keep the applied supply pressure at least 0.5 – 1 bar

above the pressure which is required to move the pneu-
matic actuator to its end position.

If fluctuations are greater, the control parameters measured
with the

X.TUNE function are not optimum.

• during operation keep the fluctuations of the supply

pressure as low as possible (max. ±10%).

9.3. safety positions

The safety position after failure of the electrical auxiliary power
depends on the fluid connection of the actuator to the working con-
nections A1 or A2.

9.3.1. single-acting actuators

actuator system

safety positions after failure of the

electrical aux-

iliary power

pneumatic

auxiliary power

up

down

down

Connection
according to
“Fig. 17”

down

up

Connection
according to
“Fig. 18”

Control function A

up

down

up

Connection
according to
“Fig. 17”

up

down

Connection
according to
“Fig. 18”

Control function B

Tab. 10: Safety positions - single-acting actuators