Electrical connection

10.4. electrical connection with cable

gland

11 +

12 –

81
82

31 +

32 –

A

B

+

+24 V

GND

remote

sensor

Fig. 21: Designation of the screw-type terminals

10.4.1. connection of the terminals

Unscrew the 4 screws on the housing cover and remove the
cover.
The screw-type terminals are now accessible.

Connect terminals according to the configuration.

10.4.2. Terminal assignment for input signals

from the control centre (e.g. plc)

terminal configuration on the

device side

external circuit / signal
level

11 +

Set-point
value +

11 +

+ (0/4 – 20 mA)
not galvanically isolated

12 –

Set-point
value GND

12 –

GND set-point value

81 +

Binary input + 81 +

+

0 – 5 V (log. 0)
10 – 30 V (log. 1)

82 –

Binary input – 82 –

GND (identical with the
GND supply voltage)

Tab. 15: Terminal assignment; input signals of the control centre