Burkert Type 8791 User Manual

Page 31

Advertising
background image

31

Electrical connection

10.4.3. Terminal assignment for output

signals to the control centre (e.g. plc)
- (required for analogue output option
only)

terminal configuration on the

device side

external circuit / signal
level

31 +

Analogue
feedback +

31 +

+ (0/4 – 20 mA)
not galvanically isolated

32 –

Analogue
feedback GND

32 –

GND (identical with the
GND supply voltage)

Tab. 16: Terminal assignment; output signals to the control centre

10.4.4. Terminal assignment for operating

voltage

terminal configuration external circuit / signal level

+24 V

Operating
voltage +

24 V DC ± 10 %
max. residual ripple 10%

+24 V

GND

GND

Operating
voltage GND

Tab. 17: Terminal assignment; operating voltage

10.4.5. Terminal assignment for connecting

the external position sensor (for remote
model only)

terminal configuration

on the
device side

external circuit / signal
level

S +

Supply
sensor +

S +

+

Remote
Sensor
Type
8798

8)

S –

Supply
sensor –

S –

A

Serial interface,
A cable

A

A-line

B

Serial interface,
B-cable

B

B-line

8)

Assignment of the wire color see “Tab. 19”

Tab. 18: Terminal assignment; external position sensor

positioner
terminal

Wire color remote
sensor with cable
type 1

Wire color remote
sensor with cable
type 2

S +

brown

brown

S –

white

black

A

green

red

B

yellow

orange

Tab. 19: Assignment of the wire color (Remote Sensor)