Refer to “fig. 22”), Head screws and circlips (refer to “fig. 22”) – Burkert Type 8798 User Manual
Page 24
24
Installation
Attachment
points for
support plate
with assembly
bridge
Support plate
Assembly
bridge
(consists of 4
parts which can
be adjusted to
the actuator
by varying the
arrangement)
Swivel
actuator
Attachment
points for
assembly bridge
with swivel
actuator
Fig. 22: Fitting the rotating Remote Sensor to a swivel actuator
measurement range of the rotating remote sensor:
The rotating Remote Sen-
sor’s measurement range
of 180° is located on the
opposite side of the power
output.
Fig. 23: Measurement range of the rotating Remote Sensor
If the X.TUNE ERROR 5 message is indicated on the
graphics display of the position controller after the X.TUNE
function starts, the sensor is not correctly aligned with the
shaft of the actuator.
• Check the alignment. The zero crossing of the sensor
must not be exceeded.
• Then repeat the X.TUNE function.
English