Start-up, Safety instructions – Burkert Type 8798 User Manual

Page 34

Advertising
background image

34

Start-Up

10.3. electrical connection of the

rotating remote sensor to the
position controller Type 8791 or
Type 8792/8793

If necessary, shorten the cable of the Remote Sensor or extend it
to a maximum of 10 m and connect it to the designated M12 cable
gland on the position controller Type 8791 or Type 8792/8793.

Connect the 4 wires of the cable, as described in “Tab. 7” and in
the operating instructions of the position controller Type 8791 or
Type 8792/8793, to the appropriate terminals.

For potential equalization, connect the shield of the cable to the
grounding connection in the terminal compartment of the position
controller.

Wire
color

configuration

external circuit
8798

8791 or
8792/8793

brown

Supply sensor +

Brown (BN)

S +

white

Supply sensor –

White (WH)

S –

grey

Serial interface
A cable

Grey (GY)

A

pink

Serial interface
B cable

Pink (PK)

B

black

Shielding

Black (BK)

Tab. 7: Wire colors and configuration; rotating Remote Sensor

11.

sTarT-up

11.1. safety instructions

Warning!

risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar

with and completely understand the contents of the operating

instructions.

• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/

the device.

No separate steps for starting up are necessary for the Remote
Sensor Type 8798.

Carry out the steps outlined for starting up in the operating
instructions of the position controller (Chapter "

Start-up" in the

operating instructions of Type 8791 or Type 8792/8793).

English

Type 8798

Advertising