31

Fluid Installation

9.4.2. pneumatic connection for process

valves belonging to series 26xx and
27xx

Danger!

risk of injury from high pressure!
• Before dismounting pneumatic lines and valves, turn off the

pressure and vent the lines.

Working connection 2
(connection: A2)

Working connection 1
(connection: A1)

upper chamber

lower chamber

Fig. 32: Pneumatic connection series 26xx and 27xx

The length of this control line should be adapted to the
actuator size because the clearance volumes caused
by the control line can have a negative influence on the
control properties. The following is the case: the smaller the
actuator, the more sensitively the control system reacts to
the length of the pneumatic control line.

procedure:

control function a (single-acting actuator):

Connect the working connection A1 or A2

4)

of the position con-

troller Type 8791 or Type 8792/8793 to the lower chamber of the
actuator using a hose.

Attach the exhaust airline or a silencer to the upper chamber.

control function B (single-acting actuator):

Connect the working connection A1 or A2

4)

of the position con-

troller Type 8791 or Type 8792/8793 to the upper chamber of the
actuator using a hose.

Attach the exhaust airline or a silencer to the lower chamber.

control function i (double-acting actuators):

Connect working connections A1 and A2 to the respective
chambers of the actuator.

4)

in line with desired safety position (see operating instructions
Type 8791 or Type 8792/8793)