Wiring a version with cable gland, English – Burkert Type 8012 User Manual

Page 33

Advertising
background image

33

Installationandwiring

Type 8012

12-36 VDC

+

-

(*)

1

2

3

4

5

blue

grey

white

brown

Power supply

Load

Fig. 11 : PNP wiring of the pulse output of a version with M12 fixed

connector

12-36 VDC

+

-

+

-

(*)

1

2

3

4

5

Power supply

brown

blue

black

grey

4-20mA

input at

external

device

Fig. 12 : Wiring the current output in sinking mode (by default) on a

version with M12 fixed connector.

12-36 VDC

+

-

+

-

(*)

1

2

3

4

5

Power supply

black

blue

grey

brown

4-20mA

input at

external

device

Fig. 13 : Wiring the current output in sourcing mode on a version

with M12 fixed connector

(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /

50 V capacitor between the negative power supply terminal and the earth.

7.4.3. Wiring a version with cable gland

color of the
wire

bn (brown)

Wh
(white)

Gn (green) ye (yellow)

Gy
(grey)

Signal on a
version with
pulse output

V+ (12-36 V DC) 0 V DC

Functional
earth

Not connected

NPN or
PNP

Signal on a
version with
pulse and
current outputs

V+ (12-36 V DC) 0 V DC

Functional
earth

Current in mA

NPN or
PNP

English

Advertising
This manual is related to the following products: