Adjustmentandfunctions

Type 8012

9.2.2. switching function

The pulse output of the 8012 can be parametered to switch a solenoid
valve or activate an alarm.
The following parameters can be preset:
• hysteresis or window operating, inverted or not
• the switching thresholds, low and high
• immediate or delayed switching

hysteresis operating
The output status changes when a threshold is reached:
• by increasing flow rate, the output status changes when the high

threshold is reached.

• by decreasing flow rate, the output status changes when the low

threshold is reached.

The behaviour of the output depends on the output wiring, NPN or
PNP.

Not inverted

Contact

Low

threshold

High
threshold

ON

OFF

Inverted

Contact

Low

threshold

High
threshold

ON

OFF

Fig. 18 : NPN pulse output, hysteresis operating, non inverted and

inverted

Not inverted

Contact

Low

threshold

High
threshold

ON

OFF

Inverted

Contact

Low

threshold

High
threshold

ON

OFF

Fig. 19 : PNP pulse output, hysteresis operating, non inverted and

inverted

Window operating
The output status changes when either threshold is reached. The
behaviour of the output depends on the output wiring, NPN or PNP.

Not inverted

Contact

Low

threshold

High
threshold

ON

OFF

Inverted

Contact

Low

threshold

High
threshold

ON

OFF

Fig. 20 : NPN pulse output, window operating, non inverted and

inverted

English