39

Adjustmentandfunctions

Type 8012

9.3.

current output

The current output, if one exists, can be parametered with the following
functions:
• an extended output range or the current output range corresponding

to a flow range

• an attenuation of the current variations, different from that of the

basic versions.

9.3.1. extension of the current range

The current output of the device can be configured to deliver a current
varying from 4 to 21.6 mA, depending on the paddle-wheel rotation
frequency.

mA

0

f (Hz)

21,6

4

275

250

20

22

300

Fig. 25 : Curve for the current proportional to the paddle-wheel

rotation frequency

9.3.2. conversion of the frequency into a

flow rate

The 8012 can be parametered to convert the paddle-wheel rotation
frequency into a flow rate, in a unit specific to the application.
In this case, the 8012 is parametered with the K factor of the device
and the desired flow rate unit.
The following flow units are available:
l/s, l/min., l/h, m

3

/min., m

3

/h, Ga/s, Ga/min., Ga/h, USGa/s,

USGa/min., USGa/h.
The current output then delivers a current of 4 to 20 mA or 4 to 21.6 mA
proportional to a flow rate range:

Flow rate (l/min., for
example)

mA

0

20

4

800

10

880

21,6

Fig. 26 : Curve for the current proportional to the flow rate