Output wirings, Output 4-20ma – Burkert Type 8056 User Manual

Page 11

Advertising
background image

SE56

11

24V COMMON

+24V INTERNAL

mA

9 (+)

10 (-)

I

4-20mA OUT

Output 4-20mA

‰

Opto-insulated output

‰

Maximum load: 1000Ÿ

‰

Maximum voltage without load: 27V

‰

Refresh frequency is the same of the sample
frequency of the connected sensor

‰

Protected against persistent over voltages to
maximum 30V

There is a transmitter load CHECK on the 4–20mA output; to disable this

function set the value "mA v.fault" to 0 (Pos. 4.4)

OUTPUT WIRINGS

NOTE: for the inputs and outputs wirings is recommended the use of shielded cables.

Output on/off 1250Hz

‰

Opto-insulated output with floating collector and
emitter terminals freely connectable

‰

Maximum switching voltage: 40V

‰

Maximum switching current: 100mA

‰

Maximum saturation voltage between collector
and emitter @100mA: 1.2V

‰

Maximum switching frequency (load on the
collector or emitter, RL=470

Ω, VOUT=24V ):

1250Hz

‰

Maximum reverse current bearable on the input
during and accidental polarity reversion (VEC):
100mA

‰

Insulation from other secondary circuits: 500V

16 (out1)
18 (out2)

17 (out1)
19 (out2)

43V

Advertising
This manual is related to the following products: