Burkert Type 8056 User Manual

Page 15

Advertising
background image

SE56

15

The ML 110 allows to show a 5 digit character display for flow rate units; this mean the
maximum flow rate value that can be represented on the display is 99999 (no matter the
positioning of the decimal point). The minimum one is 0.0025.

The representable measure unit depends from sensor flow rate and diameter; the
permitted units are those, set the instrument full scale value, allow to be represented with
a numerical field which the maximum value do not exceed 99999.

Example for DN 300:

-

Full scale value: 3m/s

-

PERMITTED measure unit (example): l/s (216.00); m

3

/h (777.60); m

3

/s (0.2160)

-

NOT PERMITTED measure unit (example): l/h (777600)..

FLOW RATE VISUALIZATION

Advertising
This manual is related to the following products: